Soft Starter application

2015-08-01

Application of ANSLE Soft starter ASR2 Series

Varieties of Application Loads

This soft start can meet the requirements of most heavy loads. The table below is for reference only.

Varieties of Application Loads Start Ramp Time (S) Stop Ramp Time (S) Inception Voltage (%) Voltage Start (Maximum Current-limiting Value) Current-limiting Start
Centrifugal Pump 16 20 40 4 2.5
Ball Grinder 20 6 60 4 3.5
Fan 26 4 30 4 3.5
Piston Type Compressor 16 4 40 4 3
Light Load Motor 16 2 30 4 3
Elevating Mechanism 6 10 60 4 3.5
Mixer 16 2 50 4 3
Crusher 16 10 50 4 3.5
Screw Compressor 16 2 40 4 3
Spiral Conveyor 20 10 40 4 2
Leather Belt Conveyer 20 10 40 4 2.5
Heat Pump 16 20 40 4 3